The UK has seen three general kinds of domestic electricity meter: very old mechanical meters (with dials or mechanical counters) that have no lights, moderately-old digital meters that still need to be read, and now “smart” meters that transmit their readings automatically. The more recent two of these three (the moderately-old digital meters and the “smart” meters) both tend to have flashing lights, but the meaning of the lights is different.
On a “smart” meter, the meaning of the lights may vary with manufacturer, and in some cases indicates signal transmission status rather than energy use. But on a moderately-old digital meter (typically installed for consumption or microgeneration before some time in the 2010s), the light usually flashes a set number of times per kilowatt-hour (kWh), typically 1000 impulses (imp) per kWh. You can multiply the time between two flashes by 1000 to find the time it will take to “clock up” 1 kWh at the current usage rate, but if you’d rather have everything in watts (and you do not possess a wireless energy monitor, or there is insufficient wiring-board room to install one), then you can use:
Average kW = 3.6 / seconds per flash
(or, if you have a metronome, kW = 0.06*BPM)
For example:
Period Wattage
1s (60 BPM) 3.6kW
1.5s (40 BPM) 2.4kW
2s 1.8kW
3s 1.2kW
4s 900W
5s 720W
6s 600W
8s 450W
10s 360W
15s 240W
20s 180W
30s 120W
1min 60W
2min 30W
For the rarer 800 imp/kWh meters, use kW = 4.5 / seconds per flash (or 0.075*BPM). In case there are any meters out there with other imp/kWh values, the general formula is kW = 3600/(imp/kWh) / seconds per flash (or 60/(imp/kWh) * BPM), but it seems 1000 imp/kWh is most common (at least in 2014).
I put up this page because there seemed to be some misinformation going around, for example:
If an imp/kWh light is lit continuously then this indicates no current flow (but some meters show this as no light rather than a continuous light). In some cases an extremely small current (such as a Raspberry Pi B+ playing audio to non-amplified speakers) will count as “no current”, but the meters are usually quite sensitive.
Some two-rate meters used in the UK's Economy 7 (e.g. 5246C) also have a second light, confusingly placed near the maximum-current label (e.g. 100A), which is always lit continuously when the off-peak circuit is energised, regardless of whether or not it’s being used. The primary imp/kWh light is the only one whose flashing or continuity indicates use or no use.